H07ZZ-F LSZH RUBBER FLEXIBLE CABLE
Availability:
In Stock
Condition:
New
Request Quote
Logo Netherlands

he H07ZZ-F cable, renowned for its Low Smoke Zero Halogen (LSZH) composition, serves as a reliable alternative to the H07RN-F Rubber Flexible cable. It offers comparable flexibility for power distribution while addressing fire safety concerns.

Designed to withstand various environmental challenges, this versatile cable is suitable for installations where fire, smoke, and toxic fumes pose risks to life and equipment. It can withstand medium mechanical stresses, making it suitable for both indoor and outdoor use. From supplying mobile power units to UPS installations and stage lighting, it caters to diverse applications.

Moreover, its resilience against water and weather conditions makes it an ideal choice for worksites and industrial plants with high human traffic or valuable assets


Technical Details:

UPC: 120000058
Seller SKU: bnc0000060
Condition: New
Availability: In Stock
Minimum order quantity: 100
Date first listed on Zandaux: Jun 19, 2024




CONDUCTOR : Plain Copper  STRANDING : Class 5  INSULATION : LSZH

OUTERSHEATH : LSZH  OUTERSHEATH COLOUR : Black

 RATED VOLTAGE 450/750v  CORE IDENTIFICATION : Black


MINIMUM BENDING RADIUS : Fixed: 4 x overall diameter Flexed: 6 x overall diameter


OPERATING TEMPERATURE : Fixed: -20°C to +90°C Flexed: -5°C to +50°C


STANDARDS : EN 50525-3-21, HD 22-13, CEI 20-19 Part 13, EN 60228 Flame Retardant according to IEC/EN 60332-3-10





Batt Part No.

Core

Size

Colour/Reference

22019

1

70

Black

22025

1

95

Black

22032

1

95

Black

22035

1

120

Black

22018

1

150

Black

22038

1

150

Black

22040

1

185

Black

22042

1

240

Black

22024

1

300

Black

22026

1

300

Black

22496

3

1.5

Black

22497

3

2.5

Black

22519

3

6

Black

22508

4

2.5

Black

22498

4

16

Black

22499

4

25

Black

22500

4

35

Black

22501

4

70

Black

22003

4

95

Black

22004

4

120

Black

22502

5

1.5

Black

22503

5

10

Black

22504

5

16

Black

22517

5

25

Black

22505

7

1.5

Black


BATT Part No

NO. OF CORES

NOMINAL CROSS SECTIONAL AREA mm

NOMINAL OVERALL DIAMETER mm

NOMINAL WEIGHT kg/km

A2 GLANDS Brass

A2PL GLAND Plastic

22032

1

95

23.4

1290

32

40

22035

1

120

25.7

1592

40

40

22038

1

150

28.3

1957

40

40

22040

1

185

31

2350

50S

50

22042

1

240

34.45

3099

50

63

22026

1

300

37.7

3687

50

 

CONDUCTORS

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS SECTIONAL AREA mm2

MAXIMUM DIAMETER OF WIRES IN CONDUCTOR mm

MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC - Plain Wires ohms/km

1

0.21

19.5

1.5

0.26

13.3

2.5

0.26

7.98

4

0.31

4.95

6

0.31

3.3

10

0.41

1.91

16

0.41

1.21

25

0.41

0.78

35

0.41

0.554

50

0.41

0.386

70

0.51

0.272

95

0.51

0.206

120

0.51

0.161

150

0.51

0.129

185

0.51

0.106

240

0.51

0.0801

300

0.51

0.0641

400

0.51

0.0486

500

0.61

0.0384

 

ELECTRICAL CHARACTERISTICS (1mm2 to 2.5mm2)

Current Carrying Capacity and Mass Supportable

NOMINAL CROSS SECTIONAL AREA mm

CURRENT CARRYING CAPACITY Amps - Single-Phase AC

CURRENT CARRYING CAPACITY Amps - Single-Phase AC

MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CABLE (See Regulations 522.7.2 and 559.6.1.5 of the 17th Edition of IEE Wiring Regulations) kg

1

10

10

5

1.5

16

16

5

2.5

25

20

5

 

Voltage Drop

NOMINAL CROSS SECTIONAL AREA mm2

mDC OR SINGLE-PHASE AC mV/A/m

HREE-PHASE AC mV/A/m

1

46

40

1.5

32

27

2.5

19

16

The above table is in accordance with Table 4F3B of the 18th Edition of IEE Wiring Regulations BS7671 and IEC 60364-5-52 Conductor operating temperature: 60°C* Note *The tabulated values above are for 60°C thermoplastic or thermosetting insulated flexible cables and for other types of flexible cable they are to be multiplied by the following factors: For 90°C thermoplastic or thermosetting insulated 1.09 150°C 1.31 185°C glass fibre 1.43

 

ELECTRICAL CHARACTERISTICS (4mm2 and above)

Current Carrying Capacity

NOMINAL CROSS SECTIONAL AREA mm2

DC OR SINGLE-PHASE AC (1 TWO CORE CABLE WITH OR WITHOUT PROTECTIVE CONDUCTOR) Amps

THREE-PHASE AC (1 THREE CORE, FOUR CORE OR FIVE CORE CABLE) Amps

SINGLE-PHASE AC OR DC (2 SINGLE CORE CABLES TOUCHING) Amps

4

42

37

 

6

55

49

 

10

76

66

 

16

103

89

 

25

136

119

 

35

 

146

200

50

 

177

250

70

 

225

310

95

 

273

369

120

 

316

432

150

 

363

497

185

 

414

564

240

 

487

673

300

 

560

773

400

 

 

924

500

 

 

1062

 

DE-RATING FACTORS

90ºC Thermosetting (Rubber) Insulated Cables

AMBIENT TEMPERATURE

35ºC

40ºC

45ºC

50ºC

55ºC

60ºC

65ºC

70ºC

75ºC

80ºC

85ºC

DE-RATING FACTOR

0.95

0.91

0.86

0.82

0.78

0.7

0.64

0.57

0.5

0.4

0.28