Our YMvK range meets stringent industry standards for the Dutch market, including NEN1010 and KEMA certification. Featuring flame-retardant PVC sheathing and XLPE insulation for temperatures up to +90°C, our cables ensure safety and reliability in fixed installations, conduits, trays, or ducts. Ideal for low-voltage applications in commercial buildings or private homes, our cables offer durability and easy installation in areas not requiring mechanical protection. 


Technical Details:

UPC: 120000123
Seller SKU: bnc0000125
Condition: New
Availability: In Stock
Minimum order quantity: 100
Date first listed on Zandaux: Jun 24, 2024
  • CONDUCTOR:  Plain Copper


    INSULATION:  XLPE                                   OUTERSHEATH: PVC


    OUTERSHEATH COLOUR: Grey               RATED VOLTAGE: 0.6/1kV


    CORE IDENTIFICATION: 

    2 core: Brown and Blue

    3 core: Brown, Blue and Green / Yellow

    4 core: Black, Grey, Brown and Green / Yellow

    5 core: Black, Blue, Brown, Grey and Green / Yellow

    Optional: 4 core - Black, Brown, Blue and Green / Yellow)


    MINIMUM BENDING RADIUS: 10 x overall diameter


    OPERATING TEMPERATURE: 

    Maximum 90°C, minimum bending 0°C / Short circuit temperature 250°C


    STANDARDS: HD 604 Part 4 Section D







    Batt Part No.

    Core

    Size

    Colour/Reference

    16592

    2

    1.5

    Grey

    16698

    2

    2.5

    Grey

    16699

    3

    1.5

    Grey

    16700

    3

    2.5

    Grey

    16487

    3

    4

    Grey

    16884

    3

    6

    Grey

    16917

    3

    10

    Grey

    16918

    3

    16

    Grey

    16701

    4

    1.5

    Grey

    16147

    4

    2.5

    Grey

    16703

    4

    4

    Grey

    16704

    4

    6

    Grey

    16705

    4

    10

    Grey

    16787

    4

    16

    Grey

    16907

    4

    35

    Grey

    16909

    4

    50

    Grey

    16024

    4

    120

    Grey

    16706

    5

    1.5

    Grey

    16271

    5

    2.5

    Grey

    16707

    5

    4

    Grey

    16272

    5

    6

    Grey

    16932

    5

    10

    Grey

    16941

    5

    16

    Grey

    16970

    7

    1.5

    Grey

    16971

    7

    2.5

    Grey

    16973

    12

    1.5

    Grey

    16974

    12

    2.5

    Grey

    16978

    24

    1.5

    Grey

    16979

    30

    1.5

    Grey









    BATT Part No

    No. of Cores

    Nominal cross sectional area of conductor (mm2)

    Radial thickness of insulation (mm)

    Nominal thickness of oversheath (mm)

    Approx overall diameter (mm)

    Weight

    16592

    2

    1.5

    0.70

    1.4

    9.3

    121

    16698

    2

    2.5

    0.70

    1.4

    10.1

    151

    16699

    3

    1.5

    0.70

    1.4

    9.4

    130

    16700

    3

    2.5

    0.70

    1.4

    10.3

    170

    16487

    3

    4

    0.70

    1.4

    11.2

    227

    16884

    3

    6

    0.70

    1.4

    12.6

    306

    16917

    3

    10

    0.70

    1.4

    14.6

    461

    16918

    3

    16

    0.70

    1.5

    17.6

    685

    16701

    4

    1.5

    0.70

    1.4

    10.2

    157

    16147

    4

    2.5

    0.70

    1.4

    11.1

    205

    16703

    4

    4

    0.70

    1.4

    12.2

    280

    16704

    4

    6

    0.70

    1.4

    13.7

    380

    16705

    4

    10

    0.70

    1.5

    15.8

    573

    16787

    4

    16

    0.70

    1.5

    19.1

    855

    16907

    4

    35

    0.90

    1.8

    26.1

    1756

    16909

    4

    50

    1.00

    1.9

    29.9

    2348

    16024

    4

    120

    1.20

    2.3

    44.2

    5618

    16706

    5

    1.5

    0.70

    1.4

    11.5

    199

    16271

    5

    2.5

    0.70

    1.4

    12.6

    262

    16707

    5

    4

    0.70

    1.4

    13.8

    357

    16272

    5

    6

    0.70

    1.4

    15.1

    468

    16932

    5

    10

    0.70

    1.5

    18.4

    744

    16941

    5

    16

    0.70

    1.6

    21.4

    1075

    16970

    7

    1.5

    0.70

    1.8

    12.5

     

    16971

    7

    2.5

    0.70

    1.8

    13.7

     

    16973

    12

    1.5

    0.70

    1.8

    15.8

     

    16974

    12

    2.5

    0.70

    1.8

    17.5

     

    16978

    24

    1.5

    0.70

    1.8

    24.6

     

    16979

    30

    1.5

    0.70

    1.8

    22.1

     


    • ELECTRICAL CHARACTERISTICS

    Nominal cross sectional area (mm2)

    Current carrying capacity (In Ground)

    Current carrying capacity (In Air)

    Max conductor DC resistance at 20°C (ohm/km)

    1.5

    30

    24

    12.1

    2.5

    24

    32

    7.41

    4

    52

    42

    4.61

    6

    64

    53

    3.08

    10

    86

    73

    1.83

    16

    11

    93

    1.15

    35

    173

    160

    0.524

    50

    205

    195

    0.387

    120

    390

    407

    0.124